Instructions and points of attention
Check that the energy meter is correctly connected to the CT (current transformer) before setting up the energy meter.
The white wire / S1 of the transformer must be connected to the + terminal of the energy meter.
The black wire / S2 of the transformer must be connected to the – terminal of the energy meter.
Attention!
If connected incorrectly, there is a possibility that the current will be measured incorrectly. For example, when you connect the black wire to the positive terminal of the energy meter.
See also the following article: Manual Eastron energy meters
Password validation
Display | Key | Description |
---|---|---|
Long press the E key to activate the setting mode. | ||
Set the password using the M and P keys. The default password is 1000. | ||
Long press the E key to confirm the password. If the password is correct, you will be taken to the slave-id menu. |
Hint!
Any change in the settings is saved by holding down the E key for 3 seconds.
Change Slave ID
Display | Key | Description |
---|---|---|
Long press the E key to activate the setting mode. | ||
The meter has two communication address modes:
| ||
Long press the E key to activate the setting mode. | ||
Use the M and P keys to set the communication address:
| ||
Long press the E key to confirm. |
Single Communications Mode
Display | Key | Description |
---|---|---|
Long press the E key to activate the setting mode. | ||
Use the M and P keys to set the communication address. Address range: 001~247 (default 001). | ||
Long press the E key to confirm. |
Multi-Communications Mode
Display | Key | Description |
---|---|---|
Long press E key to activate the setting mode. | ||
Press the M and P keys to choose the channel to be set (CH01-CH04). | ||
Press the M and P keys to set the address. Address range: 001~247 (default 001). | ||
Long press the E key to confirm. |
CT Clamp Setting
Display | Key | Description |
---|---|---|
Long press E key to activate the setting mode. | ||
Press the M and P keys to choose the channel to be set (CH01-CH04). | ||
Long press the E key to enter the setting interface of CT1 of each stage. | ||
Press the M and P keys to select the phase (L1, L2, L3). | ||
Long press the E key to enter the setting interface of CT1. | ||
Press the M and P key to set the CT1 value. CT1 range: 1~9999 A (default 100 A). | ||
Long press the E key to confirm. |
Attention!
To avoid errors in the energy measurement, the P1 port of the CT must be pointed towards the power supply. However, if the P2 port is facing the power supply, you can still correct it using the energy meter settings.