Instructions
Check that the energy meter is correctly connected to the RC (Rogowski Coil) before setting up the energy meter.
The red chip / S1 of the coil must be connected to the + terminal of the energy meter.
The black chip / S2 of the coil must be connected to the – terminal of the energy meter.
Attention!
If connected incorrectly, there is a possibility that the current will be measured incorrectly. For example, when you connect the black wire to the positive terminal of the energy meter.
You can set the meter with the following buttons:
Key | Description |
---|---|
Selects the Voltage and Current displays. In setup mode, this is the Left or Back button. | |
Selects the display screens for Frequency and Power Factor. In setup mode, this is the Up button. | |
Selects the power supply displays. In setup mode, this is the Down button. | |
Selects the energy displays. In setup mode, this is the Enter or Right button. |
Institutions
Display | Key | Description |
---|---|---|
Long press the E key to activate the setting mode. | ||
You will then be asked to enter a password. | ||
In the event of an incorrect password, this message appears on the screen. |
Menu option selection
Key | Description |
---|---|
| Use these keys to scroll through the different options of the settings. |
Press to confirm your selection. | |
| If a part is blinking, it can be adjusted with these buttons. |
When you have selected an option from the current layer, press this button to confirm your choice. The SET indicator appears. | |
Once you've set a parameter, press it to return to a higher menu level. | |
After setting, press this key repeatedly until the measurement display appears. |
Rogowski Coils Primary Current Input
The primary current runs from 1A to 5000A. The unit has 3 selectable power scales:
At a primary current lower than 500A, the CT1 (primary) must be set to 0.5kA.
At a primary current of 500A to 1000A, the CT1 should be set to 1kA.
At a primary current of 1000A to 5000A, the CT1 should be set to 5kA.
Attention!
The SDM630MCT-RC works directly with Rogowski coils without an integrator. The ratio of the connected Rogowski coils should be 85mV/kA as standard.
The CT setting of the meter must be set according to the Rogowski coil used.
To find the correct CT1 setting you can use the following table:
Model | Rated Current | Rated Output | Type |
---|---|---|---|
ESCT-RC16 | 100A | 50mV/kA | C |
ESCT-RC24 | 300A | 50mV/kA | C |
ESCT-RC36 | 600A | 50mV/kA | C |
ESCT-RC45 | 500A | 85mV/kA | D |
ESCT-RC60 | 500A | 85mV/kA | A |
ESCT-RC100 | 1000A | 85mV/kA | B |
ESCT-RC105 | 1500A | 85mV/kA | A |
ESCT-RC150 | 3000A | 85mV/kA | B |
ESCT-RC200 | 6000A | 85mV/kA | B |
ESCT-RC240 | 10000A | 85mV/kA | A |
Setting up CT1
Display | Key | Description |
---|---|---|
Use these keys in the setting menu to select the CT option. | ||
Press this key to enter the selection routine for the primary current of the CT: 0.5kA → 1kA → 5kA. | ||
Press this key. The SET indicator will appear to confirm the selection. |