This article explains the process of configuring Modbus RTU and implementing a RS-485 connection to a Calculus C06 gateway.
Objective
A technician must be able to place the SGC 120 / SGC 121 safely in configuration mode, set the correct Modbus parameters, and connect the RS-485 wiring correctly to the C06.
Scope
This guide covers the DEIF SGC 120, SGC 120 Mk II and SGC 121 for Modbus RTU configuration and the physical RS-485 connection to a Calculus C06. Configuration of the Calculus gateway in the platform is outside the scope of this document.
Compatibility
The Modbus RTU wiring and settings in this guide apply to SGC 120, SGC 120 Mk II and SGC 121. Menu labels can differ slightly by model or firmware. SGC 110 is not covered because it does not provide the RS-485 port used in this procedure.
1. Safety first
Warning
Make sure the generator cannot start unexpectedly. Put the controller in MANUAL and de-energise wiring work where required. Follow the safety procedures of the generator manufacturer/OEM.
If the controller is in
AUTOmode, pressSTOPto return toMANUAL.Disconnect the RS-485 connector before installing or changing the communication wiring.
Do not touch mains, generator or power terminals while carrying out these steps.
2. Standard Modbus settings
Use the settings below for Calculus installations on the SGC 120 / SGC 121.
Parameter | Value |
|---|---|
Protocol | Modbus RTU |
Server/Slave ID | 1 |
Baud rate | 9600 bps |
Data bits | 8 |
Parity | None |
Stop bit | 1 |
Serial format | 9600 / 8N1 |
Depending on the controller version, the display may show Server ID or Modbus Slave ID. For Calculus, set the address to 1. The communication format used is 9600 / 8N1.
3. Buttons on the SGC 120 / SGC 121

4. Configure Modbus on the DEIF SGC 120 / SGC 121
Follow the steps below on the controller. Do not change generator, protection or application parameters that are not mentioned in this procedure.

Put the controller in
MANUAL
If the controller is inAUTOmode, pressSTOPto return toMANUAL.Open Configuration mode
HoldSTOP / CONFIGfor at least 3 seconds.Press
STARTto continue
This opens the configuration / write mode so parameters can be changed.Enter the password
Use 0123 for Level 1 / full read-write access. Use▲and▼to select a digit andSTARTto confirm.
If 0123 does not work
The factory password may have been changed by the generator manufacturer/OEM. Use the known OEM password or contact the responsible party - do not reset or change unrelated settings to force access.
Open the communication settings
On SGC 120 Mk II useModule→Communication. On SGC 120 / SGC 121 use theRS485 COMM / Communicationmenu. Set only the parameters shown below.
Menu parameter | Setting |
|---|---|
Communication Mode / COMM MODE | Modbus |
Server ID / MODBUS SLAVE ID | 1 |
Baud rate / BAUDRATE | 9600 |
Parity Bit / PARITY | None |
Save and exit Configuration mode
HoldSTOP / CONFIGto return toMANUAL. Wait until saving has completed.
Result
The DEIF controller is now ready for Modbus RTU communication with address 1 and communication format 9600 / 8N1.
5. Connect RS-485 to the Calculus C06
The SGC 120 and SGC 121 use a 2-wire, half-duplex RS-485 port. The relevant connections are terminal 16 (A) and terminal 15 (B).
SGC 120 / 121 | Function | C06 | Wire |
|---|---|---|---|
Terminal 16 | RS-485 A | C06 A+ / Data+ | Brown |
Terminal 15 | RS-485 B | C06 B- / Data- | White |
No separate RS-485 GND | - | C06 GND | Green (normally not connected) |
Important
Do not connect the green C06 GND wire to DEIF terminal 1 for this point-to-point connection. Terminal 1 is the power ground - the Modbus port itself is documented on terminals 15 and 16.

Termination
The SGC 120 / SGC 121 documentation specifies termination on the RS-485 port. For SGC 120 Mk II or non-standard bus topologies, verify the actual controller and DEIF wiring documentation before adding any additional 120 ohm resistor.
6. Cabling
Use a suitable RS-485 cable with a twisted pair for Data+ and Data-.
Keep the data cable away from power cables, contactors, starter motor wiring and other sources of electrical interference.
Use the cable shield according to the installation standard; normally connect the shield to earth at one side only.
Make sure the conductors are firmly secured and that no loose copper strands can cause a short circuit.
For termination, follow the DEIF documentation for the installed controller version and bus topology. Do not add an extra 120 ohm resistor by default without checking the existing termination.
Note on A/B labels
A/B, +/-, and Data+/Data- are not labelled consistently by all manufacturers. For this installation, use: DEIF terminal 16 (A) to C06 A+ / Data+, and terminal 15 (B) to C06 B- / Data-.
7. Check after installation
Visual check Terminal 16 runs to C06 A+ and terminal 15 to C06 B-. No loose or damaged conductors.
Check settings Communication Mode = Modbus, ID = 1, Baud rate = 9600, Parity = None.
Exit configuration The controller has left Configuration mode and is back in the required operating mode.
Connect the gateway Reinstall the C06 RS-485 connector and power the installation according to the applicable procedure.
Check communication During commissioning, verify that valid Modbus data is received from the DEIF controller.
8. Troubleshooting
Problem | Possible cause | Check / action |
|---|---|---|
No communication | A/B swapped or wired incorrectly | Check 16 → A+ (brown) and 15 → B- (white). |
No communication | Serial settings do not match | Check ID 1, 9600 baud, 8 data bits, parity None, 1 stop bit. |
Cannot enter configuration | Controller not in | Press |
Password 0123 does not work | OEM changed the password | Use the known OEM password or request it from the generator manufacturer. |
Intermittent communication | Interference or poor wiring | Check twisted pair, cable routing, connections and shielding. |
Connector appears reversed | Viewing direction of the loose C06 connector | Follow function and wire colour, not only left/right position. |
9. Quick reference for the technician
SGC 120 / SGC 121 Modbus
MANUAL → STOP / CONFIG (≥ 3 s.) → START → password 0123 → Communication → Modbus → ID 1 → Baud rate 9600 → Parity None → save and exit
Settings
Protocol: Modbus RTU
Server / Slave ID: 1
Baud rate: 9600
Parity: None
Frame: 8N1
Connection
DEIF 16 (A) → C06 A+ / Data+ (brown)
DEIF 15 (B) → C06 B- / Data- (white)
C06 GND (green) → normally not connected
Check termination before adding an extra 120 ohm resistor
Final check
Controller safe and in the correct operating mode
Modbus settings correct
A/B wiring correct
Connector firmly installed
Communication confirmed during commissioning
Sources and technical verification
DEIF - Documentation for SGC 120
DEIF - Documentation for SGC 121
DEIF - SGC 120 Mk II User Manual and online documentation
DEIF - SGC 120/121 User Manual 4189341226C; Calculus - RS-485 / Modbus RTU connection; Calculus - Installing C06 in a generator
Technical values checked on 21/09/2026. If the controller firmware or OEM configuration differs, always verify against the current DEIF documentation.