Mounting the C06

Mount the C06 in the bottom right of the generator using a DIN rail.

Electrical control panel showcasing various components and a highlighted control unit.

Attaching the antenna

Drill a hole in the roof of the generator to route the antenna cables inside.
Route the antenna cables through the hole.
Attach the antenna to the roof of the generator with the nut provided.

Slide a gland over the antenna cables on the inside of the generator.
Route the antenna cables through a gland opening in the generator's wall.

Attention!

If there are no more free swivel openings, make an opening yourself.

Place the swivel in the opening.
Route the antenna cable into the cable tray.

Close-up of electrical connections and wires labeled X10 on machinery component.

Close-up of electrical cables entering a junction box with protective fittings.

Route the cables to the C06 (see photo below for cable route).

Electrical control panel showcasing various components and connections for operational functionality.

Connect the antenna cables to the antenna terminals on the top of the C06:

  • Blue → GPS (antenna socket 1)

  • Yellow → WiFi (antenna socket 2)

  • Red → LTE Main (antenna socket 4)

Connections on the Impulse C06 device, highlighting ports for GPS, WiFi, and LTE.

Attaching RS485 cable

Connect the RS485 cable to the top-left three-prong connector on the C06:

  • Green → GND (left)

  • White → B- (middle)

  • Brown → A+ (right)

Wiring connections on the Impulse C06 device with labeled ports and indicators.

Route the cable to the cable board (see photo below for cable route).

Electrical panel with wiring connections and an impulse controller at the bottom.

Connect the cable to the generator cable board:

  • Brown → Terminal 29

  • Green → Terminal 30

  • White → Terminal 31

Wiring connections in a control panel with labeled terminals and various colored cables.

Attaching the power supply

Connect the power cables to the two-prong connector on the top right of the C06:

  • Blue → GND (left)

  • Red → + (right)

Impulse C06 device with highlighted connections for power and status indicators.

Route the power cables to the cable board (see photo below for cable routing).

Wiring connections and components in an electrical control panel with highlighted elements.

Connect the power cables to the generator cable board:

  • Red → Terminal 1

  • Blue → Terminal 2

Close-up of wires connected to a green terminal block with numbered slots.